HQ3851DP type differential pressure transmitter with remote transmission equipment is a new type of intelligent transmitter produced by five-star red flag instrument ningbo digital display regulator manufacturer , important Zhejiang digital display regulator manufacturer raw materials, electronic devices and parts are imported, the entire Yuyao digital display regulator manufacturer equipment has undergone rigorous assembly and testing. the product has the characteristics of structural design, complete types, specifications and models, simple installation and application, etc.
because this model completely combines the structural advantages of two kinds of intelligent transmitters (Rosemount 3051 and Yokogawa EJA), which are popular in China at present, and are widely used in appearance, users have a refreshing feeling. in addition, it can be immediately replaced with traditional 1151, CECC and other product series in installation, and has strong practicability and replacement work ability.
potential. this product series not only has exquisite design scheme, but also has the intelligent system function of HART fieldbus agreement.
at the adoption level:
1, zui is better to use double flange plate single capillary
2, if it is high temperature machinery and equipment, the substances in the capillary must be heat resistant, otherwise it will lead to measurement deviation
at the installation level:
double flange liquid level transmitter is a kind of liquid level meter testing instrument which is widely used in the present stage. Because of the necessity of the production process and the economic development of the raw materials of the pressure guide pipe, the double flange liquid level transmitter is often installed on the spot where the standard is relatively extreme in the work. The proper installation of the level transmitter and the pressure-tapping line directly affects the accuracy of the measurement.
in order to obtain a good installation of zui, the following matters should be paid attention to:
1. avoid immediate contact between intelligent transmitter and corrosive or over-temperature substances to be measured;
2. avoid accumulation of residue in the pressure guide tube;
3. the pressure guide tube should be as short as possible;
4. The liquid column pressure head in the pressure guide pipe on both sides should remain stable;
5. The pressure guide pipe should be installed in an area with small fluctuation of temperature gradient and ambient humidity and no impact and vibration.
the ways to reduce the deviation are as follows:
1. the pressure guide tube should be as short as possible;
2. when accurately measuring liquid or vapor, the pressure guide tube should be connected upward to the step processing process pipeline, and its slope should not be less than 1/12;
3. For accurate measurement of steam, the pressure guide pipe should be connected downward to the process pipeline of the step, and its slope should not be less than 1/12;
4. The arrangement of the liquid pressure guide pipe should be prevented from appearing higher, and the arrangement of the vapor pressure guide pipe should be prevented from appearing lower;
5. the two pressure guide pipes should maintain the same temperature;
6. in order to prevent friction hazards, the specification of the pressure guide pipe should be sufficient and large;
7. there should be no vapor in the pressure guide pipe filled with liquid;
8. when the isolation liquid is applied, the level gauges of the pressure guide tubes on both sides shall be the same.
9. When cleaning the working pressure socket and pressure-inducing hole of the intelligent transmitter, trichloroethylene or ethanol should be introduced into the pressure-inducing hole, and the liquid should be gently shaken, and then the liquid should be taken out several times. It is strictly prohibited to insert any tools or instruments into the pressure-tapping hole to prevent damage to the highly sensitive sensing element. 10. Pay attention to maintaining the smart transmitter and locating the cable. When applied on the spot in industrial production, it is proposed to apply metal hose maintenance or empty racks. Be sure not to loosen the cable; locate the web-end sealing screw cap to prevent moisture from entering.